Bear Customer first, High quality first in mind, we perform closely with our consumers and provide them with efficient and experienced services for Water Filter Membrane , Filtration System , Water Treatment Systems , Winning customers' trust is definitely the gold key to our good results! If you are fascinated in our products, make sure you sense absolutely free to go to our web site or make contact with us.
18 Years Factory Waste Water Filter System - UF Membrane Module 9 inch PVDF Ultrafiltration Membrane Module UFf2860 Replacing Project – Bangmo Detail:
Applications
Drinking treatment of tap water, surface water, well water and river water.
Pretreatment of RO.
Treatment, recycle and reuse of industrial waste water.
Filtration Performance
This product is proven to have below filtering effects according to the service?conditions of different water sources:
Ingredient |
Effect |
SS, Particles?> 1μm |
Removal Rate?≥ 99% |
SDI |
≤ 3 |
Bacteria, Viruses |
>?4 log |
Turbidity |
< 1NTU |
TOC |
Removal Rate: 0-25% |
*Above data is obtained under the condition that feeding water turbidity is < 25NTU.
Product Parameters
Technical Parameters
Filtering?Type |
Outside-in |
Membrane?Material |
Modified?PVDF |
MWCO |
200K Dalton |
Membrane?Area |
52m2 |
Membrane?ID/OD |
0.8mm/1.3mm |
Dimensions |
Φ225mm* 1860mm |
Connector?Size |
DN50 Clamping; Air?Inlet?– 10mm?air?pipe |
Application Data
Pure?Water?Flux |
8,000L/H?(0.15MPa, 25C) |
Designed?Flux |
40-120L/m2.hr?(0.15MPa, 25C) |
Suggested?Working?Pressure |
≤ 0.2MPa |
Maximum?Transmembrane?Pressure |
0.15MPa |
Maximum?Backwashing?Pressure |
0.15MPa |
Air?Washing?Volume |
0.1-0.15N m3/m2 .hr |
Air?Washing?Pressure |
≤ 0.1MPa |
Maximum?Working?Temperature |
45C |
PH?Range |
Working: 4-10; Washing: 2-12 |
Operating?Mode |
Cross?Flow?or Dead End |
Feeding Water Requirements
Before feeding water, a security filter < 50 μm should be set to prevent blockage caused?by large particles in raw water.
Turbidity |
≤ 25NTU |
Oil?&?Grease |
≤?2mg/L |
SS |
≤ 20mg/L |
Total?Iron |
≤?1mg/L |
Continuous?Residual?Chlorine |
≤?5ppm |
COD |
Suggested?≤ 500mg/L |
*Material of UF membrane is polymer organic plastic, there must not be any organic solvents in raw water.
Operating Parameters
Backwashing?Flow?Rate |
100-150L/m2.hr |
Backwashing?Frequency |
Every?30-60min. |
Backwashing?Duration |
30-60s |
CEB?Frequency |
0-4?times per day |
CEB?Duration |
5-10min. |
CIP?Frequency |
Every 1-3 months |
Washing?Chemicals: |
Sterilization |
15ppm Sodium Hypochlorite |
Organic?Pollution?Washing |
0.2%?Sodium Hypochlorite + 0.1% Sodium Hydroxide |
Inorganic?Pollution?Washing |
1-2% Citric?Acid/0.2% Hydrochloric?Acid |
Component Material
Component |
Material |
Membrane |
Modified?PVDF |
Sealing |
Epoxy?Resins |
Housing |
UPVC |
Product detail pictures:
Related Product Guide:
We believe that long term partnership is a result of high quality, value added service, rich experience and personal contact for 18 Years Factory Waste Water Filter System - UF Membrane Module 9 inch PVDF Ultrafiltration Membrane Module UFf2860 Replacing Project – Bangmo , The product will supply to all over the world, such as: Lahore, Mauritius, Slovakia, Our company always concentrate on the development of the international market. We have a lot of customers in Russia , European countries, the USA, the Middle East countries and Africa countries. We always follow that quality is foundation while service is guarantee to meet all customers.